FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
STRUCTURE
System: Flag Drop Type Fault Indicator
Indication & Reset operation: The fault signal generated by the outer protective relay contacts excites the operating coil and
drop the indication flag in the annunciator. The display window of the flag changes from the
normal condition of black to the fault condition of orange.
Pushing up the reset lever returns the indicator flag to the original position, and window
returns to normal condition black, if the fault signal was monentary and operating coil is not
excited any more.
Indication pattern: However if the fault signal is continuous and still excites the operating coil, indicator flag in the
display window change to stripe pattern in orange and black by operating the reset lever. After
the fault signal is disappear the flag automatically return to the normai condition black.
●Operation
→ : Manual resetting
Normal condition Fault condition Continuous fault condition
(Black) (Orange) (Stripe pattern) → : Automatic resetting
SPECIFICATIONS (RATINGS, PERFORMANCE)
Specification Type Voltage operation type Current operation type
Rated insulation voltage (Ui) 250V
Voltage 24V, 48V, 100 / 110V, 125V, 200 / 220V AC / DC, 240V AC -
Coil rating
Current - 0.5A, 0.7A, 1.0A, 2.0A DC
Continuous input range 24V, 48V AC / DC: 80 to 130% Others: 70 to 130% 90 to 100% (in case of continuous input)
Operating value Rating X 70% max. Rating X 90% max.
Returning value Rating X 10% or more Rating X 10% or more
Minimum input pulse width (rated voltage or current) 30 msec max. 30 msec max. (200% input of rated current, 10 msec max.)
External Terminal Faston #250 or screw terminal (M3.5)
Max. wire size 2mm2 max. (AWG14)
Insulation resistance 10MΩ or more (Between electric circuit block and ground) / 5MΩ or more (electric circuit between each other / Between contact terminals [Between poles])
Power frequency Withtand voltage 2,000V AC (Between electric circuit block and ground / electric circuit between each other) / 1,000V AC (Between contact terminals [Between poles]) / 1 min.
Lightning impulse withstand voltage ±4.5kV (Between electric circuit block and ground / electric circuit between each other) / ±3kV (Between contact terminals [Between potes]) / 3 times for each poles (1.2 / 50µs)
Overload capability Rating X 1.3 times / 3 hours / 1 time Rating X 6.0 times / 30 sec. / 1 time
Contact current-carrying capacity 2A
Contact breaking capacity 110V DC, 0.2A (L/R = 7msec)
Vibration resistance Frequency: 16.7Hz, Width of frequency: 4mm, 10 min for each axis
Shock resistance 294m/s2, 3 times each axial direction
Durability 10,000 times or more (electrical, mechanical)
Protection degree Panel surface: IP40
Ambient operating temperature 0 to 40°C (‒10 to 55°C: a few hours are allowed per day)
Storing temperature ‒20 to 60°C
Relative humidity 30 to 80% (average per day, no dew condensation)
Altitude 2,000 m max.
Weight 300g
B54
E CONTROL D ELECTRONIC AMP & DEVICES C
CONNECTING
CENTER PARTS DEVICES B
PILOT L
INDICATOR A SWITCH
Page2
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
FEATURES HOW TO ORDER
The panel back size is shorter than The approximately 40% expansion of ■How to order as single unit
TK type by about 25%. the name character area enhances
visibility of a nameplate.
24mm 28mm ZK - 120A - DC110V XX - OBF
133mm 100mm
Basic type
Surface frame
Contact arrangements Rated voltage / current B: Black
(For further details, see Page B60.) Voltage operation type
Code Flag interlock Coil interlock Code Coil rating Resistance value Flag color
000A - - DC024V 24V DC 270Ω O: Yellow-red (orange)
TK Type ZK Type (Faston tab type) 010A - 1a DC048V 48V DC 1080Ω When coil excitation continues after reset operation,
020A - 2a DC110V 100 / 110V DC 4800Ω the flag color turns pattern black and orange.
030A - 3a DC125V 125V DC 6900Ω
110mm 020D - 1a1b DC220V 200 / 220V DC 19500Ω Special specification Rear surface terminal
100A 1a - AC024V 24V AC 270Ω Code Description Code Description
110A 1a 1a AC048V 48V AC 1080Ω
TK Type ZK Type XX Standard specification S Screw terminal (M3.5)
120A 1a 2a AC110V 100 / 110V AC 4800Ω
120D 1a XZ F
1a1b AC125V 125V AC 6900Ω Varistor mounted type Faston tab #250
(Voltage type only)
A plug-in method for internal elements 120E 1a 2b AC220V 200 / 220V AC 19500Ω
is adopted, which enables easy - AC240V 240V AC 24100Ω XZ type is special.
200A 2a
220A 2a 2a Note: Voltage type AC rated product has a built-in
changing of specifications and 800V rated rectifier.
210A 2a 1a
Current operation type
Any contact arrangements other than those above
ZK Type (screw type) maintenance from the front of the are available. Code Coil rating Resistance value
panel. DC0.5A 0.5A DC 4.4Ω
DC0.7A 0.7A DC 2.1Ω
DC1.0A 1.0A DC 1.0Ω
Faston / Tab type and Screw type DC2.0A 2.0A DC 0.28Ω
are available as standard line up.
Screw type is equiped with a
terminal cover.
Vertical and horizontal jumper for link ■How to order internal elements
reduce wires.
ZK - U - 120A - DC110VXX - O
Short time input operation is Flag color
available for current type. O: Yellow-red (orange)
Basic type Internal element When coil excitation continues after
(operating at 200% or more of rated current, reset operation, the flag color turns
When removing the internal element, hang an pattern black and orange.
at input pulse of 10 msec). element unplugging tool on the lower hook to unplug Contact arrangements Rated voltage / current
It sensitively responds to an pulse by lifting and removing the lock. (For further details, see Page B60.) Voltage operation type Special specification
Code Flag interlock Coil interlock Code Coil rating Resistance value Code Description
input signal to the annunciator relay. 000A - - DC024V 24V DC 270Ω XX Standard specification
For further details, refer to technical 010A - 1a DC048V 48V DC 1080Ω XZ Varistor mounted type
information (page B62). 020A - 2a DC110V 100 / 110V DC 4800Ω
XZ type is special.
Measures for whisker trouble are fully 030A - 3a DC125V 125V DC 6900Ω
prepared by eliminating the use of tin 020D - 1a1b DC220V 200 / 220V DC 19500Ω
100A 1a - AC024V 24V AC 270Ω
and zinc plating. 110A 1a 1a AC048V 48V AC 1080Ω
120A 1a 2a AC110V 100 / 110V AC 4800Ω
4 cotacts can be choosed from 2 120D 1a 1a1b AC125V 125V AC 6900Ω
120E 1a 2b AC220V 200 / 220V AC 19500Ω
contacts linked with the display flag 200A 2a - AC240V 240V AC 24100Ω
and 3 contacts linked with the coil 220A 2a 2a Note: Voltage type AC rated product has a built-in
800V rated rectifier.
210A 2a 1a
voltage. Any contact arrangements other than those above Current operation type
Wide contact variations enable to Collective mounting is available, which are available. Code Coil rating Resistance value
DC0.5A 0.5A DC 4.4Ω
omit some auxiliary relays now in saves hole cutting work one by one.
DC0.7A 0.7A DC 2.1Ω
use. It contributes to reduce man-hour. DC1.0A 1.0A DC 1.0Ω
(A vertical one-line assembly is not available). DC2.0A 2.0A DC 0.28Ω ●Internal element
B55
15mm
21mm
Page3
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
FEATURES HOW TO ORDER
The panel back size is shorter than The approximately 40% expansion of ■How to order as single unit
TK type by about 25%. the name character area enhances
visibility of a nameplate.
24mm 28mm ZK - 120A - DC110V XX - OBF
133mm 100mm
Basic type
Surface frame
Contact arrangements Rated voltage / current B: Black
(For further details, see Page B60.) Voltage operation type
Code Flag interlock Coil interlock Code Coil rating Resistance value Flag color
000A - - DC024V 24V DC 270Ω O: Yellow-red (orange)
TK Type ZK Type (Faston tab type) 010A - 1a DC048V 48V DC 1080Ω When coil excitation continues after reset operation,
020A - 2a DC110V 100 / 110V DC 4800Ω the flag color turns pattern black and orange.
030A - 3a DC125V 125V DC 6900Ω
110mm 020D - 1a1b DC220V 200 / 220V DC 19500Ω Special specification Rear surface terminal
100A 1a - AC024V 24V AC 270Ω Code Description Code Description
110A 1a 1a AC048V 48V AC 1080Ω
TK Type ZK Type XX Standard specification S Screw terminal (M3.5)
120A 1a 2a AC110V 100 / 110V AC 4800Ω
120D 1a XZ F
1a1b AC125V 125V AC 6900Ω Varistor mounted type Faston tab #250
(Voltage type only)
A plug-in method for internal elements 120E 1a 2b AC220V 200 / 220V AC 19500Ω
is adopted, which enables easy - AC240V 240V AC 24100Ω XZ type is special.
200A 2a
220A 2a 2a Note: Voltage type AC rated product has a built-in
changing of specifications and 800V rated rectifier.
210A 2a 1a
Current operation type
Any contact arrangements other than those above
ZK Type (screw type) maintenance from the front of the are available. Code Coil rating Resistance value
panel. DC0.5A 0.5A DC 4.4Ω
DC0.7A 0.7A DC 2.1Ω
DC1.0A 1.0A DC 1.0Ω
Faston / Tab type and Screw type DC2.0A 2.0A DC 0.28Ω
are available as standard line up.
Screw type is equiped with a
terminal cover.
Vertical and horizontal jumper for link ■How to order internal elements
reduce wires.
ZK - U - 120A - DC110VXX - O
Short time input operation is Flag color
available for current type. O: Yellow-red (orange)
Basic type Internal element When coil excitation continues after
(operating at 200% or more of rated current, reset operation, the flag color turns
When removing the internal element, hang an pattern black and orange.
at input pulse of 10 msec). element unplugging tool on the lower hook to unplug Contact arrangements Rated voltage / current
It sensitively responds to an pulse by lifting and removing the lock. (For further details, see Page B60.) Voltage operation type Special specification
Code Flag interlock Coil interlock Code Coil rating Resistance value Code Description
input signal to the annunciator relay. 000A - - DC024V 24V DC 270Ω XX Standard specification
For further details, refer to technical 010A - 1a DC048V 48V DC 1080Ω XZ Varistor mounted type
information (page B62). 020A - 2a DC110V 100 / 110V DC 4800Ω
XZ type is special.
Measures for whisker trouble are fully 030A - 3a DC125V 125V DC 6900Ω
prepared by eliminating the use of tin 020D - 1a1b DC220V 200 / 220V DC 19500Ω
100A 1a - AC024V 24V AC 270Ω
and zinc plating. 110A 1a 1a AC048V 48V AC 1080Ω
120A 1a 2a AC110V 100 / 110V AC 4800Ω
4 cotacts can be choosed from 2 120D 1a 1a1b AC125V 125V AC 6900Ω
120E 1a 2b AC220V 200 / 220V AC 19500Ω
contacts linked with the display flag 200A 2a - AC240V 240V AC 24100Ω
and 3 contacts linked with the coil 220A 2a 2a Note: Voltage type AC rated product has a built-in
800V rated rectifier.
210A 2a 1a
voltage. Any contact arrangements other than those above Current operation type
Wide contact variations enable to Collective mounting is available, which are available. Code Coil rating Resistance value
DC0.5A 0.5A DC 4.4Ω
omit some auxiliary relays now in saves hole cutting work one by one.
DC0.7A 0.7A DC 2.1Ω
use. It contributes to reduce man-hour. DC1.0A 1.0A DC 1.0Ω
(A vertical one-line assembly is not available). DC2.0A 2.0A DC 0.28Ω ●Internal element
B56
15mm
21mm
E CONTROL D ELECTRONIC P & DEVICES C
CONNECTING
CENTER PARTS DEVICES B
PILOT LAM
INDICATOR A SWITCH
Page4
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
■How to order as assembled products STANDARD PRODUCTS
Collective mounting is available for ZK type. It is not neccessary to make holes for each units,
and the assembled units can be installed in only one hole. ZK(Faston type) ●Outline
Mounting panel (t=1 to 6mm) Nameplate
1 In case of assembling the same specification holder
ZK - 02 x 03 - 120A - DC110VXX - OBF
Basic Vertical Horizontal Contact Rated voltage,
type number number arrangement Current
Display
window
2 In case of assembling different specifications
Please enter the order sheet for ZK Drop Type Annunciator Relay attached to the page B63. Type NP Fitting tool
Tab terminal
#250 series Reset lever
ZK - 02 x 03 - MIX - MIX - OBF Mounting hole size
〈When mounting a single unit〉
Basic Vertical Horizontal Contact Rated voltage,
type number number arrangement Current
Order Sheet for ZK Type Fault Indicator ●Accessories
1 to 2 to 8
3 stages stages Internal element ZK-U- -
Nameplate ZK-DP
Please refer to the above type coding for orders. Element unplugging tool TK-NQ
Please write “MIX” in “Contact arrangement” in Fitting tool ZK-TK(standard equiment
case of assembling different specifications of )
contact arrangement.
Please write “MIX” in “Rated voltage, current”
in case of assembling different specifications
of rated voltage, current
About the layout drawing
Enclose the shape of the assembled window in ZK(Faston type [collective]) ●Outline
the layout drawing with a continuous line.
Fitting tool Mounting panel (t=1 to 6mm)
About the layout configuration
Fill the contact arrangement, rated voltage and
current, and rear terminal in the layout
configuration.
Precaution for assemblies
When ordering a collective type of rear terminal symbols S
(screw specification), please order after taking the wire size
and number of wires into account (there is a possibility that
wiring may be difficult depending on the wire size and Rating . Contact arrangement NP
(In case different ratingscontact arrangements are mixed,
number of wires). sealed under lower surfare)
Table of sizes (mm) Contact arrangement
Coil rating
Horizontal stage number
2 row 3 row 4 row 5 row 6 row 7 row 8 row Mounting hole size
L1 72 108 144 180 216 252 288 ●Accessories
L2 70
Sizes of collective mounting L3 81 Internal element ZK-U- -
Refer to the right table as to sizes of collective mounting L1 72 108 144 180 216 252 288
when mounting collectively. L2 140 Nameplate ZK-DP
A virtical one-line assembly is not available. L3 151 Element unplugging tool TK-NQ
L1 72 108 144 180 216 252 288
L2 210 Fitting tool ZK-TK(standard equiment)
L3 221
Single row is not available.
B57
Vartical stage number
Third Second First
stage stage stage
Page5
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
■How to order as assembled products STANDARD PRODUCTS
Collective mounting is available for ZK type. It is not neccessary to make holes for each units,
and the assembled units can be installed in only one hole. ZK(Faston type) ●Outline
Mounting panel (t=1 to 6mm) Nameplate
1 In case of assembling the same specification holder
ZK - 02 x 03 - 120A - DC110VXX - OBF
Basic Vertical Horizontal Contact Rated voltage,
type number number arrangement Current
Display
window
2 In case of assembling different specifications
Please enter the order sheet for ZK Drop Type Annunciator Relay attached to the page B63. Type NP Fitting tool
Tab terminal
#250 series Reset lever
ZK - 02 x 03 - MIX - MIX - OBF Mounting hole size
〈When mounting a single unit〉
Basic Vertical Horizontal Contact Rated voltage,
type number number arrangement Current
Order Sheet for ZK Type Fault Indicator ●Accessories
1 to 2 to 8
3 stages stages Internal element ZK-U- -
Nameplate ZK-DP
Please refer to the above type coding for orders. Element unplugging tool TK-NQ
Please write “MIX” in “Contact arrangement” in Fitting tool ZK-TK(standard equiment
case of assembling different specifications of )
contact arrangement.
Please write “MIX” in “Rated voltage, current”
in case of assembling different specifications
of rated voltage, current
About the layout drawing
Enclose the shape of the assembled window in ZK(Faston type [collective]) ●Outline
the layout drawing with a continuous line.
Fitting tool Mounting panel (t=1 to 6mm)
About the layout configuration
Fill the contact arrangement, rated voltage and
current, and rear terminal in the layout
configuration.
Precaution for assemblies
When ordering a collective type of rear terminal symbols S
(screw specification), please order after taking the wire size
and number of wires into account (there is a possibility that
wiring may be difficult depending on the wire size and Rating . Contact arrangement NP
(In case different ratingscontact arrangements are mixed,
number of wires). sealed under lower surfare)
Table of sizes (mm) Contact arrangement
Coil rating
Horizontal stage number
2 row 3 row 4 row 5 row 6 row 7 row 8 row Mounting hole size
L1 72 108 144 180 216 252 288 ●Accessories
L2 70
Sizes of collective mounting L3 81 Internal element ZK-U- -
Refer to the right table as to sizes of collective mounting L1 72 108 144 180 216 252 288
when mounting collectively. L2 140 Nameplate ZK-DP
A virtical one-line assembly is not available. L3 151 Element unplugging tool TK-NQ
L1 72 108 144 180 216 252 288
L2 210 Fitting tool ZK-TK(standard equiment)
L3 221
Single row is not available.
B58
Vartical stage number
Third Second First
stage stage stage
E CONTROL D ELECTRONIC DEVICES C
CONNECTING
CENTER PARTS DEVICES B
PILOT LAMP &
INDICATOR A SWITCH
Page6
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
STANDARD PRODUCTS CONTACT ARRANGEMENTS AND SEQUENCES
ZK(Screw type) ●Outline About contact arrangement
Contact arrangement
symbol Operation chart
Mounting panel (t=1 to 6mm) Nameplate
holder Terminal No.
ZK-120A Momentary fault Continuous fault
Coil operation
(+)9 7 5 3 1 9-10
1-2
3-4
Contact operation
30
, 5-6 ZK-110A Momentary fault Continuous fault
a2 a2 a1 7-8
RESET Manual reset operation (+)9 7 5 3 1 9-10
Display (-)10 8 6 4 2
window Indication 1-2
3-4
Contact Target indication
arrangement Black 30 5-6
circuit Stripe pattern
a2 a1
Orange
Terminal cover 7-8
1 : Contact which interlocked with flag
Type NP Fitting tool RESET
2 : Contact which interlocked with coil (-)10 8 6 4 2
Reset lever
Screw with 30 : Coil (Terminals # 9 and #10 fixed in all models) Indication
a square
washer
●Accessories ZK-000A Momentary fault Continuous fault ZK-120A Momentary fault Continuous fault
Mounting hole size (+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
〈When mounting a single unit〉 Internal element ZK-U - 1-2 1-2
3-4 3-4
Nameplate ZK-DP 30 5-6 30
, 5-6
7-8 a2 a2 a1 7-8
Element unplugging tool TK-NQ RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Terminal cover ZK-CV(standard attachment) Indication Indication
Momentary fault Continuous fault Momentary fault Continuous fault
Fitting tool ZK-TK(standard attachment) ZK-010A ZK-120D
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
Crimp terminal ZK-STSET(10 pcs attached) 1-2 1-2
3-4 3-4
Jumper ZK-SBV(Vertical linking) 30 5-6 30 5-6
a2 7-8 b2 a2 a1 7-8
Jumper ZK-SB36,50(Horizontal linking) RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Indication Indication
ZK-020A Momentary fault Continuous fault ZK-120E Momentary fault Continuous fault
ZK(Screw type [collective]) (+)9 7 5 3 1 9-10
●Outline (+)9 7 5 3 1 9-10
1-2 1-2
Fitting tool Mounting panel (t=1 to 6mm)
3-4 3-4
30
, 5-6 30 5-6
a2 a2 7-8 b2 b2 a1 7-8
RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Indication Indication
ZK-030A Momentary fault Continuous fault ZK-200A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
3-4 3-4
Terminal 30 5-6 30
cover ,, , , 5-6
a2 a2 a2 7-8 a1 a1 7-8
RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Rating . Contact arrangement NP Indication Indication
(In case different ratingscontact arrangements are mixed,
sealed under lower surfare)
Contact arrangement Momentary fault Continuous fault Momentary fault Continuous fault
Coil rating ZK-020D ZK-220A
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
Mounting hole size ●Accessories
3-4 3-4
Internal element ZK-U - 30 5-6 30
b2 a2 , , 5-6
7-8 a2 a2 a1 a1 7-8
Nameplate ZK-DP RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Element unplugging tool TK-NQ Indication Indication
ZK-100A Momentary fault Continuous fault ZK-210A Momentary fault Continuous fault
Terminal cover ZK-CV(standard attachment)
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
Fitting tool ZK-TK(standard attachment) 1-2 1-2
3-4 3-4
Crimp terminal ZK-STSET(necessary pcs attached) 30 5-6 30
, 5-6
a1 a2 a1 a1
7-8 7-8
Jumper ZK-SBV(Vertical linking) RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Jumper ZK-SB36(Horizontal linking) Indication Indication
∗ Any contact arrangements other than those above are available. Please feel free to inquire.
B59
Page7
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
STANDARD PRODUCTS CONTACT ARRANGEMENTS AND SEQUENCES
ZK(Screw type) ●Outline About contact arrangement
Contact arrangement
symbol Operation chart
Mounting panel (t=1 to 6mm) Nameplate
holder Terminal No.
ZK-120A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 Coil operation
1-2
3-4
Contact operation
30
, 5-6 ZK-110A Momentary fault Continuous fault
a2 a2 a1 7-8
(+)9 7 5 3 1 9-10
Display RESET Manual reset operation
(-)10 8 6 4 2
window Indication 1-2
3-4
Contact Target indication
arrangement Black 30
Stripe pattern 5-6
circuit a2 a1
Orange
Terminal cover 7-8
1 : Contact which interlocked with flag
Type NP Fitting tool RESET
2 : Contact which interlocked with coil (-)10 8 6 4 2
Reset lever
Screw with 30 : Coil (Terminals # 9 and #10 fixed in all models) Indication
a square
washer
●Accessories ZK-000A Momentary fault Continuous fault ZK-120A Momentary fault Continuous fault
Mounting hole size (+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
〈When mounting a single unit〉 Internal element ZK-U - 1-2 1-2
3-4 3-4
Nameplate ZK-DP 30 5-6 30
, 5-6
7-8 a2 a2 a1 7-8
Element unplugging tool TK-NQ RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Terminal cover ZK-CV(standard attachment) Indication Indication
Momentary fault Continuous fault Momentary fault Continuous fault
Fitting tool ZK-TK(standard attachment) ZK-010A ZK-120D
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
Crimp terminal ZK-STSET(10 pcs attached) 1-2 1-2
3-4 3-4
Jumper ZK-SBV(Vertical linking) 30 5-6 30 5-6
a2 7-8 b2 a2 a1 7-8
Jumper ZK-SB36,50(Horizontal linking) RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Indication Indication
ZK-020A Momentary fault Continuous fault ZK-120E Momentary fault Continuous fault
ZK(Screw type [collective]) ●Outline (+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
Fitting tool Mounting panel (t=1 to 6mm)
3-4 3-4
30
, 5-6 30 5-6
a2 a2 7-8 b2 b2 a1 7-8
RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Indication Indication
ZK-030A Momentary fault Continuous fault ZK-200A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
3-4 3-4
Terminal 30
cover ,, , 5-6 30
, 5-6
a2 a2 a2 7-8 a1 a1 7-8
RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Rating . Contact arrangement NP Indication Indication
(In case different ratingscontact arrangements are mixed,
sealed under lower surfare)
Contact arrangement Momentary fault Continuous fault Momentary fault Continuous fault
Coil rating ZK-020D ZK-220A
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
Mounting hole size ●Accessories
3-4 3-4
Internal element ZK-U - 30 5-6 30
, , 5-6
b2 a2 7-8 a2 a2 a1 a1 7-8
Nameplate ZK-DP RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Element unplugging tool TK-NQ Indication Indication
ZK-100A Momentary fault Continuous fault ZK-210A Momentary fault Continuous fault
Terminal cover ZK-CV(standard attachment)
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
Fitting tool ZK-TK(standard attachment) 1-2 1-2
3-4 3-4
Crimp terminal ZK-STSET(necessary pcs attached) 30 5-6 30
, 5-6
a1 a2 a1 a1
7-8 7-8
Jumper ZK-SBV(Vertical linking) RESET RESET
(-)10 8 6 4 2 (-)10 8 6 4 2
Jumper ZK-SB36(Horizontal linking) Indication Indication
∗ Any contact arrangements other than those above are available. Please feel free to inquire.
B60
E CONTROL D ELECTRONIC DEVICES C
CONNECTING
CENTER PARTS DEVICES B
PILOT LAMP &
INDICATOR A SWITCH
Page8
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
ACCESSORIES
Element extraction tool Fitting tool (Order unit: 10)
(Order unit: 10)
●TK-NQ ●ZK-TK
Standard equipment
Jumper (Order unit: 100)
For rear terminal symbol S (screw specification)
ZK-SBV ZK-SB36 ZK-SB50
Vertical linking Horizontal linking (36mm pitch) Horizontal linking (50mm pitch)
For vertical adjacent terminals For upper stage terminals of min. pitch For upper stage terminals of
instration (36mm) or assembled type 50mm pitch instration
Terminal cover (Order unit: 100) Nameplate (Order unit: 100)
For rear terminal symbol S (screw specification) (Acryl material t = 1mm)
●ZK-CV ●ZK-DP
Commercial cardboards
are also available
21mm instead of ZK-DP.
67mm
Standard equipment
30.5mm
27.5mm
Cramp terminal (Order unit: 100)
●ZK-ST
Standard accessory for screw type (10 pcs).
B61
Page9
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
ACCESSORIES TECHNICAL DATA
Element unplugging tool Fitting tool (Order unit: 10) Operating condition of current type
(Order unit: 10)
●TK-NQ ●ZK-TK For the current operation type, it is sometimes used by connecting in series with a relay equipped
with a self-cutoff contact in the manner shown in Figure 1; in that case, current I shows the waveform
shown in Figure 2 depending on the coil inductance of those serial relays.
Voltage V waveform
Standard equipment P
Relay
Jumper Ry
(Order unit: 100)
For rear terminal symbol S (screw specification)
ZK-SBV ZK-SB36 ZK-SB50
Voltage Current waveform Calculated
V circuit current
value
Current ZK Calculated
circuit current
value
30
Vertical linking Horizontal linking (36mm pitch) Horizontal linking (50mm pitch)
For vertical adjacent terminals For upper stage terminals of min. pitch For upper stage terminals of N
instration (36mm) or assembled type 50mm pitch instration 200% or more
current of rating Rectangle
1
10 msec or more
Terminal cover (Order unit: 100) Nameplate (Order unit: 100) -PN\YL(UL_HTWSLVMJPYJ\P[JVUULJ[PVU Figure 2. Voltage and current waveform
For rear terminal symbol S (screw specification) (Acryl material t = 1mm)
●ZK-CV ●ZK-DP When high-speed operation is required (operation at 200% or more of rated current and minimum
input pulse of 10 msec or less), please select a coil rating that can secure a rectangle1 within the
Commercial cardboards actual circuit current waveform
are also available
21mm instead of ZK-DP.
67mm High-speed operation is confirmed in the condition with the resistance value of the serial relay (Fig. 1
Standard equipment Ry) in the following table.
30.5mm
27.5mm Coil rating of F ault Indicator Relay resis tance value
0.5A DC 36.7Ω
0.7A DC 26.2Ω
Cramp terminal (Order unit: 100) 1A DC 18.3Ω
●ZK-ST 2A DC 9.2Ω
Standard accessory for screw type (10 pcs).
B62
E CONTROL D ELECTRONIC DEVICES C
CONNECTING
DEVICES B
PILOT LAMP &
CENTER PARTS INDICATOR A SWITCH
Page10
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
Order Sheet for ZK Type Fault Indicator
Date of order: (month) (day), (year)
Company Person
name in charge
TEL
e-mail
FAX
Type
coding
Quantity Delivery Number of
Units time (month) (day), (year) Order
Please enclose the following layout drawing with a continuous line as the shape of an assembled window.
Please fill the contact arrangement, rated voltage, current, special use and also rear terminal in the
following layout configuration.
The sizes of the mounting hole are the horizontal outside dimension: -4 mm and the vertical outside
dimension: -5 mm.
Layout
drawing
A
A-01 A-02 A-03 A-04 A-05 A-06 A-07 A-08
B
B-01 B-02 B-03 B-04 B-05 B-06 B-07 B-08
C
C-01 C-02 C-03 C-04 C-05 C-06 C-07 C-08
Contact Rated voltage, Special Rear surface
Layout arrangement current specification terminal
configuration A-01 ZK- - -OB
A-02 ZK- - -OB
A-03 ZK- - -OB
A-04 ZK- - -OB
A-05 ZK- - -OB
A-06 ZK- - -OB
A-07 ZK- - -OB
A-08 ZK- - -OB
Contact Rated voltage, Special Rear surface
arrangement current specification terminal
B-01 ZK- - -OB
B-02 ZK- - -OB
B-03 ZK- - -OB
B-04 ZK- - -OB
B-05 ZK- - -OB
B-06 ZK- - -OB
B-07 ZK- - -OB
B-08 ZK- - -OB
Contact Rated voltage, Special Rear surface
arrangement current specification terminal
C-01 ZK- - -OB
C-02 ZK- - -OB
C-03 ZK- - -OB
C-04 ZK- - -OB
C-05 ZK- - -OB
C-06 ZK- - -OB
C-07 ZK- - -OB
C-08 ZK- - -OB
B63
Row C Row B Row A