Technical data sheet EXT-KA-SE100
Indoor Air Quality sensor Temperature /
Humidity / CO₂ / PM2.5 / PM10 / TVOC
EXT-KA-SE100 provides real-time accurate
measurements of IAQ to allow for increased
credit from building certification (e.g. LEED,
WELL, RESET). IAQ sensor comes with multiple
power, connectivity, and installation options.
EXT-KA-SE100 is equipped with 7" full colour
touchscreen display for real-time monitoring.
Technical data
Electrical data Nominal voltage USB-C (5V 1.8A DC)
Connection Ethernet IEEE 802.3 (Data rate: Up to 100 Mbps)
Connection wireless 2.4 GHz 802.11 b/g/n; security standards
supported: 64/128 WEP, WPA-PSK, WPA2-PSK,
WPA, WPA2 Personal
Battery operation Capacity and voltage: 5200 mAh @ 4.2 V
Data bus communication Communication Modbus TCP
BACnet/IP
Local and cloud MQTT
Open API
Cloud
Functional data Coverage area Area: 325 m² [3500 ft²]
Space types and layouts should be considered
in accordance with project requirements.
Display 7" Touchscreen full colour Available display
languages German, English, Chinese
Measuring data Measured values CO₂
TVOC
PM2.5, PM10
Relative humidity
Temperature
Specification Particulate Matter Sensing element technology Laser particle sensor (light scattering)
Measuring range Mass concentration range: 0...1000 μg/m³
PM2.5 mass concentration size range: 0.3...2.5
μg/m³
Accuracy ±10% of measured value (30...1000 μg/m³)
±3 μg/m³ (0...30 μg/m³)
Typical response time ≤10 s
Sensor output resolution 1 μg/m³
Specification CO₂ Sensing element technology Non-dispersive infrared (NDIR)
Measuring range 400...2000 ppm
Up to 10000 ppm extended range
Accuracy ±3% of measured value ±50 ppm
Typical response time <120 s (T90)
Sensor output resolution 1 ppm
Specification TVOC Sensing element technology Multi-pixel metal oxide sensor (MOx)
www.belimo.com EXT-KA-SE100 • en-gb • 2023-12-12 • Subject to change 1 / 4
Page2
Technical data sheet EXT-KA-SE100
Technical data
Specification TVOC Measuring range 0...60000 ppb
Accuracy ±15% ±8 ppb
Typical startup time 0.4 ms
Sensor output resolution 1 ppb
Specification Temperature Measuring range -20...100°C
Accuracy ±1°C
Long term stability <0.03°C [0.054°F]/yr (under normal RH/T
operating range)
Typical response time >2 s
Sensor output resolution 0.01°C
Specification Humidity Measuring range 0...99% RH
Accuracy ±5% RH
Long term stability <0.25% RH/yr
Typical response time >8 s (depends on the surrounding surface and
the airflow in the final application
environment)
Sensor output resolution 0.01% RH
Safety data EU Conformity CE Marking
Ambient humidity Max. 95% RH, non-condensing
Ambient temperature 0...50°C [32...122°F]
Product Features
Operating mode Temperature: Typical value for operation in normal RH/T operating range. Higher drift values
may occur due to contaminant environments with vaporised solvents, out-gassing tapes,
adhesives, packaging materials, etc. Temperature response times strongly depend on the
type of heat exchange, the surrounding surface and the airflow in the final application
environment.
Humidity: Humidity response times strongly depend on the surrounding surface and the
airflow in the final application environment.
CO₂: Extended exposure to concentrations below 400 ppm may result in incorrect operation of
ABC algorithm and should be avoided. Sensor provides readings in the extended range up to
10,000 ppm, but the accuracy may be lower than that specified in the table.
Target gas profile TVOC Complex mixture of 22 VOCs as defined by Molhave et al.
n-Hexane, n-Nonane, n-Decane, n-Undecane ,1-Octane, 1-Decene, Cyclohexane, m-Xylene,
Ethylbenzene, 1,2,4-Trimethylbenzene, n-Propylbenzene, a-Pinene, n-Pentanal, n-Hexanal,
Iso-propanol, n-Butanol, 2-Butanone, 3-Methyl-3-butanone, 4-Methyl-2-pentanone, n-
Butylacetate, Ethoxyethylacetate, 1, 2-Dichloroethane
Sampling process Diffusion
Data storage and logging Frequency of readings (log interval): 1 minute, 1 hour, 1 day
Data push interval: 1 minute (customisable upon request)
Onboard memory: 8 GB (>50,000,000 data points)
Recommended lifetime of sensor unit CO₂: 15 years
Temperature: 10 years
Humidity: 10 years
Particulate matter: 1.3 years (>200 μg/m³), 2 years (<100 μg/m³)
Warranty and durability Standard warranty: 2 years (excluding replaceable sensor module)
Expected lifespan: 5 to 7 years
www.belimo.com EXT-KA-SE100 • en-gb • 2023-12-12 • Subject to change 2 / 4
Page3
Technical data sheet EXT-KA-SE100
Remarks
General remarks concerning sensors Calibration via hot-swappable sensor modules for sensor modules
Particulate matter: Calibrated against standardised aerosol mix
TVOC: Calibrated against ethanol
Indicators and Operation
Accessories
Electrical accessories Description Type
Sensor module, PM2.5 PM10 EXT-KA-KM100
Sensor module, temperature, relative humidity, TVOC EXT-KA-KM103
Wiring diagram
www.belimo.com EXT-KA-SE100 • en-gb • 2023-12-12 • Subject to change 3 / 4